If you need to know what the signals of your American Standard furnace mean, you can find the necessary information about it here. The tables presented on this page are the lists of American Standard furnace error codes with their explanations and possible problem solutions.
The signals are sorted by LED color and number of flashes which you observe. The meanings are given for all kinds of faults, for example, 2 flashes are described as system lockout, and 3 flashes have several meanings possible. For some modifications there are also alert codes given to provide better understanding of nature of the issue.
LED Color | Fault LED | Alert Code | Description | Control Display |
---|---|---|---|---|
Red | 90 | Excessive Communication Errors | N/A | |
1 Flash | 91 | Loss of Heat/Cool Demand Message (COMM) | ERR 91 | |
Loss of Bit Master (Clock Signal) | ||||
2 Flash | Defrost Fault A | |||
3 Flash | 68 | Defrost Fault B and/or C | N/A | |
4 Flash | Defrost Fault A and [B and/or C] | |||
5 Flash | 67 | Ambient Temperature Sensor Fault (Out of Range – Open or Shorted) | ERR 67 | |
6 Flash | Coil Temperature Sensor Fault (Out of Range – Open or Shorted) | |||
Low Pressure Cut Out Fault (Open outside of defrost Cycle-Hard lock out, cycle power to reset) | ERR 79 | |||
7 Flash | 79 | Low Pressure Cut Out Fault Heat/Cool Lock out | ||
Low Pressure Cut Out Fault (Open outside of defrost Cycle-Short lock out) | Wait n | |||
10 Flash | 102 | Y2 without Y1 – Miswire (24 volt mode only) | N/A | |
11 Flash | 67 | Liquid Temperature Sensor Fault (Out of Range – Open or Shorted) | N/A | |
12 Flash | 113 | Liquid Pressure Sensor Fault (Out of Range – Open or Shorted) | ERR 113 | |
13 Flash | 67 | External Outdoor Temperature | N/A | |
Sensor Fault (Out of Range – Shorted) | ||||
PM Missing with local copy (Operational) | ERR 114 | |||
Bad Data in PM with local copy (Operational) | N/A | |||
14 Flash | 114 | Bad Data in PM no local copy (Not Operational) | ERR 114 | |
PM Missing with no local copy (Not Operational) | ||||
15 Flash * | 50 | Duplicate OD Temperature Sensor * | N/A | |
16 Flash * | 123 | Demand Configuration Fault * | N/A |
LED Color | Charge Assist™ (CA) LEDs | Flashing | Description |
---|---|---|---|
Green | CHARGED | Off | Charged or not in CA Mode |
On | Charge is Correct | ||
Y1 | On | 1 st stage compressor requests | |
Y2 | On | 2nd stage compressor request | |
Fast Flash | Initialization at Power Up ~ 60 seconds | ||
Med Flash | Oil Return Mode ** (Forced Defrost) | ||
STATUS | Slow Flash | Standard operation | |
Off | Charge Assist™ mode or no power to control | ||
LitePort | Occasional Flash | For transmitting LitePort™ data | |
Amber | COM | Flashing | Flash device count when in communication (number of COMM products connected in system); Rapid flashes followed by a pause indicates disrupted communications |
Off | No power | ||
On | Solid at power-up | ||
Flashing | See Stabilization Flash Rate | ||
CHARGING | Off | Not in CA Mode | |
ADD | On | System requires refrigerant charge (Control has 24 volt AC output to Charqe Solenoid) | |
Red | ODT | Flashing | Ambient Temperature is out of range – Ambient Temperature must be above 55°F and below 120°F to enter CA Mode A/ore: ODT LED will flash 1 sec ON/OFF for 30 seconds and the CHARGING LED will flash 5 times per second for 2 seconds, then exit CA. |
RECOVER | On | Need to recover refrigerant – Unit locked out for 1 hour or press mode button to exit Charge Assist™ | |
LOW | On | Liquid pressure below 90 psig – Liquid pressure must be above 90 psig to enter CA Mode | |
Note: LOW oressure LED will be on for 30 seconds and the CHARGING LED will flash 5 times per second for 2 seconds, then exit CA. |
LED | Description |
---|---|
2 Flashes | System Lockout (Retries or Recycles exceeded) |
3 Flashes | Draft Pressure Error – Possible problems: |
a) Venting problem | |
b) Pressure switch problem | |
c) Inducer problem | |
4 Flashes | Open Temperature Limit Switch |
5 Flashes | Flame sensed when no flame should be present |
6 Flashes | 115 volt AC power reversed, ignitor (Triac) fault, poor grounding or system voltage too low |
7 Flashes | Gas valve circuit error |
8 Flashes | Low flame sense |
9 Flashes | Open Inducer Limit switch |
10 Flashes | Inducer communication error |
Solid | Internal GV error or Low TH voltage |
Solid Red w/Solid Green “STATUS” LED | Continuous Reset caused by a blown fuse or internal error. |