Dunkirk boiler troubleshooting



Dunkirk has been manufacturing home heating products since 1928. Currently, its product range includes residential and commercial hot-water boilers, steam boilers, indirect water heaters, and more.

Dunkirk boiler troubleshooting may turn out easier than you expected provided you use a reliable guide. This is exactly what you will find below. Having identified the symptom, check it in the list and try the suggested solutions.

Dunkirk 95M-200 boiler troubleshooting

Code Reason For Soft Lockout Corrective Actions (pressing RESET should restart boiler immediately):
8 0.14″ Pressure switch contacts open 1 Check pressure switch for proper operation. Replace pressure switch if moisture has entered switch. Check venting for blockage. Clear if present.
18 High Limit Operation: Burner oft until outlet water temperature drops below 180 °F 1 Happen when heat demand is lower than lowest firing rate of boiler, such as operation of single, small zone. Check system for:
• Verify boiler and system are full of water.
• Verify system does not have trapped air.
• Inspect and verify system piping and components.
• Verify piping agrees with boiler manual recommendations.
2 Use contact thermometer to check outlet water temp. Compare to temperature shown with display in “INFO” mode (“1” in first digit). Replace return temperature sensor if results are not close. Replace control module if sensor replacement doesn’t solve problem.
19 High Limit Operation: Burner offuntil return water temp, drops below 190 °F 1 Check system for:
• Verify boiler and system are full of water.
• Verify system does not have trapped air.
• Inspect and verify system piping and components.
• Verify water flow is not reversed or pipes crossed.
2 Use contact thermometer to check return water temp. Compare to temperature shown with display in “INFO” mode (“2” in first digit). Replace return temperature sensor if results are not close. Replace control module if sensor replacement doesn’t solve problem.
High Limit Operation: Return temp, is higher than supply temp. 1 • Verify boiler and system are full of water.
• Verify system does not have trapped air.
• Inspect and verify system piping and components.
• Verify water flow is not reversed or pipes crossed.
24 2 Use contact thermometer to check return water temp. Compare to temperature shown with display in “INFO” mode (“2” in first digit). Replace return temp, sensor if results are not close. Replace control module if sensor replacement doesn’t solve problem.
High limit operation: Outlet water temp, increased too quickly. Non-adjustable default setting 9.8°F/sec 1 Indicates flow rate too low. Check system for:
• Verify boiler and system are full of water.
• Make sure system does not have trapped air.
• Inspect and verify system piping ana components.
• Verify piping agrees with boiler manual recommendations.
25 2 Verify operation of boiler circulator:
• Check voltage at circulator junction box to ensure 120 vac when boiler operates. If no voltage, check wiring and wiring connections.
• High voltage terminal strip terminals 5 and 6 should show 120 vac for space heating; terminals 3 and 4 should show 120 vac for DHW. Replace circulator if powered but not operating.
• Replace line voltage wire harness if necessary. Replace control module if wire replacement doesn’t resolve.
26 Aquastat contacts open or LWCO contacts open or 3.5″ Switch open 1 Verify proper setting of control.
Water temp too high, wait for temperature to drop below 180 degrees.
2 Check water level in boiler, fill if low.
Press LWCO reset switch on display panel
If problem still exists, check LWCO probe and board according to manufacturer’s instructions. Replace if necessary.
3 Check pressure switch for proper operation. Replace if moisture has entered switch. Check venting for blockage. Clear if present.
29 Blower turning when it should be off. 1 Check boiler wiring against wiring diagram.
Replace line voltage and low voltage wiring harnesses if necessary. Replace control module if wire replacement doesn’t resolve.
30 High limit operation: Temperature rise across boiler too high. 1 Flow rate too low.
Check system for:
Verify boiler and system are full of water.
Inspect and verify system piping and components.
Verify piping agrees with boiler manual recommendations. Make sure system pressure drop is not too high.
2 Verify operation of boiler circulator.
Check voltage at circulator junction box to ensure 120 vac when boiler operates. If no voltage, check wiring and wiring connections.
High voltage terminal strip terminals 5 and 6 should show 120 vac for space heating; terminals 3 and 4 should show 120 vac for DHW.
Replace circulator if powered but not operating.
Replace line voltage wire harness if necessary.
Replace control module if wire replacement doesn’t resolve.
61 Pressure switch contacts closed. 1 Check pressure switches for proper operation.
Replace pressure switch if moisture has entered switch.
65 Blower not operating when turned on. 1 Turn off power to boiler. Remove line voltage connector at blower. Restart boiler and check voltage across blower plug terminals. If 120 vac is NOT present, inspect wiring and tightness of connections.
Replace line voltage wire harness if necessary.
Replace control module if wire harness replacement doesn’t resolve.
2 If 120 vac is present on blower wire harness, replace harness and retry. If problem persists, replace blower motor.

Dunkirk Q90-125 boiler troubleshooting

LIGHT STATUS INDICATES
ON IBC is energized through 24 volt transformer.
POWER OFF IBC is not energized.
Blinking IBC receives more than 40 VAC.
ON IBC is energizing draft inducer and air flow is proven.
PURGE OFF Off during purge cycle – draft inducer is not powered on or air flow is not proven.
Off during igniter and run cycle – normal operation, purge cycle complete.
Blinking IBC is locked out. Problem could indicate false positive proof of air flow. Blocked vent, intake air pipe, flue way, or orifice in negative pressure hose.
ON IBC is energizing igniter.
OFF Igniter is not energized.
ON IBC is energizing gas control valve to open.
VALVE OFF Gas control valve is closed.
Blinking IBC is locked out. Problem is flame has not been proven in three (3) ignition attempts. May be due to broken igniter or lack of/low flame signal, or no gas.
On Bright Flame proven.
FLAME On Dim Checking for flame signal (during trial for ignition)
OFF Flame unproven.

Dunkirk XEB-2 boiler troubleshooting

POSSIBLE CAUSE WHAT TO DO
Thermostat is not set correctly Reset thermostat
Burner is not operating properly Check flame. If it is yellow, the burner is not getting enough air. Or, if flame is blue and noisy and seems to lift off the burner, the burner is getting too much air. Contact your service technician.
No electric power to boiler Check overcurrent protection. Check to be sure electric power supply circuit is “ON”.
Controls out of adjustment Reset according to instructions.
Radiators not heating Open radiator vents to excess air. Check flow control valve (if used). It may be in closed position.
Circulating pump not running Check overcurrent protection. Check relay operation.
Poor electrical contact Check all control terminals and wire joints.
Chimney flue is blocked Pressure switch will not close and pilot spark will not operate to start pilot. Have your service technician check and correct, if necessary.
Rollout switch blown Have your service technician check heat exchanger for blockage. Replace rollout switch with exact replacement.
Gas input amount is incorrect Contact your service technician.
Dirt on seat Open valve manually. Allow water to run and clear valve seat.
Water logged expansion tank Drain tank, see instructions.