Munchkin boiler error codes



CodesCause/Solutions
MUNCHKIN ERROR CODEAn error code may occur in the installation of the Munchkin. This condition may lead to a lock out con- dition of the controller, which will need to be manu- ally reset through the S4/Reset button. These tempo- rary codes will help the installer correct the problem before going into a lock out condition, which will require a manual reset.
BOILER ERROR1. When an error condition occurs the con- troller will display an error code on the dis- play module.
2. These error codes and several suggested corrective actions are included in Table 7.1.
3. In the case of E00, E13, and E14 this error, if uncorrected, will go into a fault condition as described is Paragraph C (Boiler Fault).
BOILER FAULT1. When a fault condition occurs the controller will illuminate the red "fault" indication light and display a fault code in the format (Example: E21) on the display module.
2. Note the fault code and refer to Table 7.2 for an explanation of the fault code along with several suggestions for corrective actions.
3. Press the reset key to clear the fault and resume operation. Be sure to observe the operation of the unit to prevent a recurrence of the fault.

CodeDescriptionCorrective Action
E00High Limit Exceeded1. Check circulation pump operation.
2. Assure that there is adequate flow through the boiler by accessing the status menu and assuring that there is less than a 50°F rise from the return thermister to the supply thermister.
3. Replace switch if faulty.
E13Combustion Fan Speed Low. The boiler combustion air fan speed less than 70% of expected.
1. Check the combustion air fan wiring.
2. Replace the combustion air fan.
3. Replace the control board.
E14Combustion Fan Speed High. The boiler combustion air fan speed is more than 130% of expected.
1. Check the combustion air fan wiring.
2. Replace the combustion air fan.
3. Replace the control board.
PROPressure Switch Open1. Assure that the system pressure is above 10 psig.
2. Check for leaks in the system piping.
FLUBlocked Vent Pressure Switch Open1. Assure that the vent is not blocked
2. Check the switch operation by applying a jumper. (If the switch is not functioning properly, replace it.)
F00High Limit Exceeded.1. Check circulation pump operation
2. Assure that there is adequate flow through the boiler by accessing the status menu and assuring that there is less than a 50°F rise from the return thermister to the supply thermister.
3. Check thermister reading on supply thermister. Replace switch if faulty.
F01Vent Temperature Limit Exceeded.1. Push the red reset button on the switch.
2. Check the flue temperature during operation using a combustion analyzer.
3. Replace the switch if faulty.
F02Interrupted or Shorted
Supply (Outlet) Thermister.
1. Check the electrical connection to the thermister on the outlet manifold.
2. Replace thermister if necessary.
F03Interrupted or Shorted
Return (Inlet) Thermister.
1. Check the electrical connection to the thermister on the inlet manifold.
2. Replace thermister if necessary.
F05Supply (Outlet)
Temperature exceeds 230T.
1. Check circulation pump operation.
2. Assure that there is adequate flow through the boiler by accessing the status menu and assuring that there is less than a 50°F rise from the return thermister to the supply thermister.
F06Return (Inlet) Temperature Exceeded 230°F.
1. Check circulation pump operation.
2. Assure that there is adequate flow through the boiler by accessing the status menu and assuring that there is less than a 50°F rise from the return thermister to the supply thermister.
F09No flame detected - The boiler will make three attempts at ignition before the control goes into this lockout condition.1. Watch the igniter through the observation window provided.
2. If there is no spark, check the spark electrode for the proper %" gap.
3. Remove any corrosion from the spark electrod and flame rectifier probe.
4. If there is a spark but no flame, check the gas supply to the boiler.
5. If there is a flame, check the flame sensor.
6. Check any flue blockage or condensate blocks.
F10Loss of Flame Signal - The boiler will relight 4 times before the control goes into this lockout condition.
1. Monitor the gas pressure to the unit while in operation.
2. Assure that the flame is stable when lit
3. Check to see if the green light on the display module is out while the boiler is running.
4. If the green light doesn't come on or goes off during operation check the flame signal on the status menu.
5. If the signal reads less than 1 microampere, clean the flame rectifier probe.
6. If the flame rectifier probe continues to read low, replace it.
F11False Flame Signal - The boiler will lock out if it senses a flame signal when there should be none present
1. Turn the gas off to the unit at the service valve.
2. If the flame signal is still present replace the igniter.
3. If the flame signal is not present after turning off the gas supply, check the gas valve electrical connection.
4. If there is no power to the gas valve, remove the valve and check for obstruction in the valve seat or replace the gas valve.
5. Turn the gas on at the service valve after corrective action is taken.
F13Combustion Fan Speed Low - The boiler will lock out if it senses that the fan speed is less than 70% of expected rate for more than 60 seconds.
1. Check the combustion air fan wiring.
2. Replace the combustion air fan.
3. Replace the control board.
F14Combustion Fan Speed High - The boiler will lock out if the fan speed is more than 130% of expected rate for more than 60 seconds.1. Check the combustion air fan wiring.
2. Replace the combustion air fan.
3. Replace the control board.
F18Gas Valve Error1. Make sure the connector is correctly connected to the gas valve.
2. Check the electrical wiring from the valve to the control board.
3. Replace the low voltage wiring harness assembly.
4. Replace control board.
F30WatchdogCall factory for further assistance.
F31Parameter MemoryCall factory for further assistance.
F32Parameter Memory Write ErrorCall factory for further assistance.
F33Programming ErrorCall factory for further assistance.