If it is difficult for you to find out the cause of a breakdown of a Raypak boiler because of absence of paper instructions, opt for our help. The troubleshooting table giving decoding to any breakdown and defining the complexity of repairs is provided below. It is a great help for both simple users and master hands.
Raypak B6000 boiler troubleshooting
Symptom | Possible Cause | Corrective Action |
---|---|---|
No Display. | No Primary power. | Check power connections to units. Check surge protection devices. Check disconnects, check grounds. Check power switches. |
* Nite set-back time display no longer correct. | Time display accidentally Re-Programmed. | Initialize system. Program Nite set-back feature. |
* Nite set-back not working properly. | Nite set-back turned off. Clock times not set. | Initialize system. |
* Time display does not maintain proper time. | System ground not adequate. Line noise. Internal battery weak. Prolonged power outage. | Initialize system and / or contact authorized Raypak Representative for further instructions. |
System not working automatically. | Boiler monitor has Manual Mode selected | Select Automatic mode on Boiler Monitor. |
Display shows incorrect number of boilers. | Inadequate grounds. Line noise Power outages. | Check primary power check wired ground. Rework as necessary. Initialize system. |
Scrambled control display. | Power outages. | Initialize system. |
Boiler does not function properly after power outage. | Internal battery weak. Line noise. System ground not adequate. | Initialize system. |
Boiler "Not on Line" displayed. | Primary power at boiler not connected. | Initialize system. |
Outdoor and water temp, readings Incorrect (-35°F). | Inadequate ground Line noise. | Initialize system. |
Power outage. | ||
Displayed parameters do not make sense. | Power outage. | Initialize system. |
System Faults indicators do not make sense. | Power outage. | Initialize system. |
Boiler # x "Not on Line" Displayed | Boiler not powered. | Check primary power. "Correct as necessary. Check communication cable, check (surge) ground Remove / Replace (R/R) as necessary. Initialize system. " |
Outdoor Temp. Sensor readings are high. | Outdoor sensor not mounted correctly. | Refer to installation manual mounting instructions. Possible relocation for sensor. |
Sensor reading 220°F. | Sensor wiring shorted | Check sensor wiring for damage. R/R as necessary. Initialize system. |
Sensor reading 35°F. | Sensor wiring open. | R/R as necessary Initialize system. |
Low water cut-off alarm. | Excessive circuit loading of pump contacts by user supplied system pump. Low water level in boiler | Check power. Check pump contactor / relay R/R as necessary. Replace F1 fusing. Check main water supply |
Power lamp off on Boiler Monitor. | Fuse F1 blown. Excessive circuit loading of pump contacts by user supplied system pump. Circuit breaker tripped. | Replace F1 fusing. Remove Relay-K1 to isolate circuit loading. R/R as necessary. Reset circuit breaker. |
Pump not running. | Excessive circuit loading of pump contacts by user supplied system pump. | Replace F1 fusing. |
Pump going off on thermal overload circuit breaker tripped | Check pump. Reset circuit breaker |
|
Off at flow switch. | Paddle damaged or missing. Pump off on thermal overload. | Check paddle on flow switch. Check pump, contact or relay. Replace F1 fusing. |
Off on High Limit. | Low limit settings. Intermittent power or pump failure. | Check and correct settings. Meter amperage on pump. R/R as needed. |
Raypak 0180B Type H boiler troubleshooting
PROBLEM | CAUSES | SOLUTIONS |
---|---|---|
1 )When room thermostat is turned on, boiler does not operate. | 1 )No power to the boiler. | 1) Check circuit breakers, disconnect switch. Make sure power is on. |
2) Defective room thermostat or disconnected wire in thermostat circuit. | 2)Check continuity on thermostat and wiring circuit. Replace thermostat, or repair wiring connections. | |
3) Defective transformer. | 3) Check secondary voltage. If no 24V, replace transformer. | |
4)Defective pump relay. | 4) Check relay coil or contacts. Replace as required. | |
5) Defective pump. | 5) Replace pump. | |
2)When room thermostat is calling for heat, pump is on. but burners will not turn on. | 1)For standing pilot models, pilot burner not lighted. | 1)Light pilot burner. (Follow lighting instructions on rating plate.) |
2)lf pilot burner will not stay lighted, thermocouple or gas valve may be defective. | 2)Check thermocouple MV generation. If less than 25MV (open circuit), replace thermocouple. If between 2535 MV. replace gas valve. | |
3) Gas knob in "Pilot" position. | 3)Turn knob to "ON” position. | |
4) For automatic ignition models, gas valve knob is in "OFF" position. | 4) Turn gas knob to "ON". If ignition module locks out. reset by interrupting power to boiler. | |
5)Vent switch is open. | 5) Check for blockage of venting system or disconnected vent piping. After problem is corrected push button to reset, or replace single-use type vent switch. | |
6)Roll-out switch is open. | 6)Check for blockage of flue or sooted heat exchanger. After problem is corrected push button to reset or replace single use type roll-out switch. | |
7)High limit is open. | 7) Setting may be too low. Check water flow and adjust setting to obtain 2030°F temperature rise. | |
8) Fast Response Temperature Sensor probe is defective. | 8) Red LED on circuit board will be ON to indicate a loose sensor connection or a shorted sensor. Check terminal connectors or replace sensor as required. | |
9) Fast Response Temperature sensor board is defective. | 9)Check voltage across output and common terminals. If no 24V is present. replace board. | |
10) Defective ignition module or defective gas valve. | 10) Before module goes into a lock-out, check voltage across MV and MV/ PV. If no 24V is present, replace module. If 24V is present, replace gas valve. | |
3) Pilot Outage. | 1) Too low or too high gas pressures. | 1) Adjust inlet gas pressure as shown on rating plate. |
(Standing pilot models) | 2) Restricted pilot. | 2) Clean pilot orifice. |
3) Weak thermocouple. | 3) Replace thermocouple. | |
4)Yellow lazy flame. | 1) Too low gas pressure. | 1) Adjust manifold pressure as shown on rating plate. |
2) Restricted burner intake ports. | 2) Clean burners free of debris or insects. | |
3) Restricted gas line. | 3) Clean gas line or increase gas line piping. | |
5) Sooting | 1) Insufficient combustion air. | 1) Refer to installation instructions regarding combustion air requirements. |
2) Improper venting. | 2) Refer to installations instructions. | |
3) Severe yellow burner flames. | 3) See yellow flame section above. |