Modern boilers are equipped with sensors and elements, which control their functioning. They activate protective mechanisms, which, in turn, prevent things from getting worse. If a malfunction does occur, please, check the table and troubleshoot it.
Code | Lockout Message | Description |
---|---|---|
E1 | Failed Ignition | The burner failed to light after 5 ignition attempts. |
E2 | False Flame | A flame is being detected prior to ignition. |
E3 | High Boiler Temperature | Boiler temperature has reached 210?F [99?C] |
E5 | Blower Speed | Blower is not at correct speed or speed signal is not being received by control module. |
E8 | Flame Circuit Error | Flame circuit test failed. |
E9 | Gas Valve Circuit Error | Gas valve circuit test failed. |
E13 | Reset Limit Reached | Resets are limited to 5 every 15 minutes. |
E15 | Sensor Drift | Supply or return sensor reading has drifted. |
E16 | Supply Sensor Stuck | Supply sensor reading is not changing. |
E17 | Return Sensor Stuck | Return sensor reading is not changing. |
E18 | Sensor Failure | Supply or return sensor reading changed very rapidly. |
E21 | Internal Control Fault | A / D conversion error. |
E30 | Supply Sensor Shorted | A short circuit has been detected in the boiler supply temperature sensor circuit. |
E31 | Supply Sensor Open | |
E43 | Return Sensor Shorted | |
E44 | Return Sensor Open | |
E80 | Return > Supply | Return temperature is higher than supply temperature. |
E87 | External Limit Open | An external manual reset limit has opened |
E7 | High Flue Temperature | Flue temperature exceeds high limit. |
E12 | Internal Control Fault | EEPROM misconfiguration |
E25 | Internal Control Fault | CRC check error. |
E32 | DHW Sensor Shorted | A short circuit has been detected in the DHW temperature sensor circuit. |
E33 | DHW Sensor Open | An open circuit has been detected in the DHW temperature sensor circuit. |
E34 | Low Voltage | Line voltage has fallen below an acceptable operating level. |
E37 | Low Water | Water level has fallen below an acceptable operating level. |
E45 | Flue Sensor Shorted | A short circuit has been detected in the boiler flue temperature sensor circuit. |
E46 | Flue Sensor Open | An open circuit has been detected in the boiler flue temperature sensor circuit. |
E76 | External Limit Open | An external automatic reset boiler limit has opened. |
E81 | Sensor Drift | Supply and return temperatures are not equal. |
E89 | Incorrect Setting | A parameter setting is in conflict with another setting. |
E90 | Firmware Mismatch | Control module and display firmware versions are incompatible. |
E91 | System Sensor Shorted | A short circuit has been detected in the system temperature sensor circuit. |
E92 | System Sensor Open | An open circuit has been detected in the system temperature sensor circuit. |
E93 | Outdoor Sensor Shorted | |
E94 | Internal Display Fault | Display memory error. |
E95 | Supply Sensor Error | Supply sensor reading is invalid. |
E96 | Outdoor Sensor Open | An open circuit has been detected in the outdoor temperature sensor circuit. |
E97 | Cascade Mismatch | Cascade configuration has changed. |
E98 | Cascade Bus Error | Communication with other boilers has been lost. |
E99 | Controller Bus Error | Communication between boiler display and control module has been lost. |