Modern gas furnaces are quite reliable appliances, but even they may be prone to some malfunctions ore breakages caused by misuse or improper maintenance. If you found out that you can’t start your Lennox gas furnace or it shows some signs of a malfunction (provides not enough heat, for instance), you might want to use our troubleshooting tips to save money on professional repair services.
Lennox ELO183DH Series Furnace Troubleshooting
Action | System Response |
---|---|
Thermostat calls for heat. (W terminal is energized.) | Oil primary control is energized. |
Ignition system and oil primary control start the furnace. Oil flows as long as cad cell senses flame. | |
Burner motor is energized and heat fan on delay timing begins. When timing is complete, the circulating fan is energized at heat speed and warm air is delivered to the controlled space. | |
Thermostat ends call for heat. (W terminal is de-energized.) | Oil primary control is de-energized, terminating the burner cycle. |
Heat fan off delay (60 to 120 seconds) timing begins. When timing is complete, the circulat- ing fan is de-energized. | |
Oil primary control and circulating fan are off. | |
Burner fails to light. | Oil primary control locks out within lockout timing (timing depends on oil primary control). Burner motor is de-energized. |
If heat fan has started, it continues through the delay off period. | |
Established flame fails. | Burner motor is de-energized and oil primary control goes into recycle mode. |
If heat fan off delay is longer than the recycle delay timing, the heat fan continues to run through the next trial for ignition. | |
Thermostat begins call for cool. (G and Y terminals are energized.) | Circulating fan is energized at the cool speed. Cooling compressor turns on immediately. |
Thermostat ends call for cool. (G and Y terminals are de-energized.) | Circulating fan and cooling compressor turn off immediately. |
Thermostat begins call for fan. (G terminal is energized.) | Circulating fan is energized immediately at cool speed. |
Thermostat ends call for fan. (G terminal is de-energized.) | Circulating fan is de-energized. |
Limit switch string opens. | Oil primary control shut off the burner. |
Circulating fan is energized immediately at heat speed. | |
Oil primary control is de-energized. | |
Circulating fan runs as long as limit string stays open. | |
If there is a call for cooling or fan, the circulating fan switches from heat speed to cool speed. | |
Limit switch string closes. | Heat fan off delay (60 to 120 seconds) begins. |
Circulating fan turns off after the selected heat fan off delay timing. Oil primary control is energized, initiating burner light off. | |
Continuous circulating fan is connected. (Optional connectors are available for separate circulating fan speed tap.) | Circulating fan is energized at low speed when there is no call for heat, cool or fan. |
Humidity control is connected. (Optional connectors are available for 120 Vac humidifier.) | Humidifier connections are energized when the burner motor is energized. |
Lennox A80UH1E Furnace Troubleshooting
RED LED Flash Code | Diagnostic Codes / Status of Furnace |
---|---|
Off | No power to control or board fault detected |
Heartbeat | Control powered – displayed during all modes of operation if no errors are detected |
1 Flash | Reverse Line Voltage Polarity |
2 Flashes | Improper Earth Ground |
3 Flashes | Burner failed to light, or lost flame during heat demand |
4 Flashes | Low Flame Signal – check flame sensor |
5 Flashes | Watchguard – burner failed to light, exceeded maximum number of retries or recycles. |
6 Flashes | Not Used |
7 Flashes | Primary or Secondary Limit Open or Watchguard Mode – Limit Switch Open Longer than 3 minutes |
8 Flashes | Rollout Switch Open |
9 Flashes | Pressure Switch failed to close or opened during heat demand |
10 Flashes | Watchguard – Pressure Switch opened 5 times during one heat demand |
11 Flashes | Pressure switch stuck closed prior to activation of combustion air inducer |
12 Flashes | Flame Sensed without gas valve energized |
13 Flashes | Low Line Voltage |
Lennox O23 Furnace Troubleshooting
Source | Procedure | Causes | Correction |
---|---|---|---|
Thermostat | Check thermostat settings. | Thermostat in OFF or COOL | Switch to HEAT. |
Thermostat is set too low | Turn thermostat to higher temperature. | ||
Safety Overloads | Check burner motor, primary safety control, & auxiliary limit switch. | Burner motor overload tripped | Push reset button pump motor. |
Primary control tripped on safety | Reset primary control. | ||
Auxiliary limit switch tripped on safety | Reset auxiliary limit. | ||
Power | Check furnace disconnect switch & main disconnect. | Open switch | Close switch. |
Blown fuse or tripped circuit breaker | Replace fuse or reset circuit breaker. | ||
Thermostat | Touch jumper wire across thermostat terminals on primary control. If burner starts, then fault is in the thermostat circuit. | Broken or loose thermostat wires | Repair or replace wires. |
Loose thermostat screw connection | Tighten connection. | ||
Dirty thermostat contacts | Clean contacts. | ||
Thermostat not level | Level thermostat. | ||
Faulty thermostat | Replace thermostat. | ||
CAD Cell | Disconnect the flame detector wires at the primary control. If the burner starts, fault is in the detector circuit. | Flame detector leads are shorted | Separate leads. |
Flame detector exposed to light | Seal off false source of light. | ||
short circuit in the flame detector | Replace detector. | ||
Primary Control | Place trouble light between the black and white leads. No light indicates that no power is going to the control. | Primary or auxiliary control switch is open | Check adjustment. Set the maximum setting. |
Jumper terminals; if burner starts, switch is faulty, replace control. | |||
Open circuit between disconnect switch and limit control | Trace wiring and repair or re- place it. | ||
Low line voltage or power failure | Call the power company. | ||
Place trouble light between the orange and white leads. No light indicates faulty control. | Defective internal control circuit | Replace the control. | |
Burner | Place the trouble light between the black and white leads to the burner motor. No light indicates that no power is getting to the motor. | Blown fuse | Replace the fuse. |
Place trouble light between the black and white leads to the blower motor. Light indicates power to the motor and burner fault. | Binding burner blower wheel | Turn off power and rotate the blower wheel by hand. If seized, free the wheel or replace the fuel pump. | |
Sized fuel pump | |||
Defective burner motor | Replace the motor. |
Lennox G1N80BU Furnace Troubleshooting
LED Status | Fault Description |
---|---|
LED Off | No power to control or control hardware fault detected |
LED On | Normal operation |
1 Flash | Flame present with gas valve off |
2 Flashes | Pressure switch closed with inducer off |
3 Flashes | Pressure switch open with inducer on |
4 Flashes | High limit switch open |
5 Flashes | Rollout switch open |
6 Flashes | Pressure switch cycle lockout |
7 Flashes | Lockout due to no ignition |
8 Flashes | Lockout due to too many flame dropouts |
9 Flashes | Incorrect line voltage phasing |
Lennox OHR23Q5 Furnace Troubleshooting
Symptoms of Abnormal Operation | Fault Description(s) | Possible Causes |
---|---|---|
– Motor rocks slightly when starting. | – This is normal start-up for variable speed motor. | — |
– Motor won’t start. | – No movement. | – Manual disconnect switch off or door switch open. |
– Blown fuse or circuit breaker. | ||
– 24 Vac wires miswired. | ||
– Unseated pins in wiring harness connectors. | ||
– Bad motor/control module. | ||
– Moisture present in motor or control module. | ||
– Motor rocks, but won’t start. | – Loose motor mount. | |
– Blower wheel not tight on motor shaft. | ||
– Bad motor/control module. | ||
– Motor oscillates up & down while being tested off of blower. | – It is normal for motor to oscillate with no load on shaft. | — |
– Motor starts, but runs erratically. | – Varies up and down or intermittent. | – Variation in 115 Vac to motor. |
– Unseated pins in wiring harness connectors. | ||
– Erratic CFM command from “BK” terminal. | ||
– Improper thermostat connection or setting. | ||
– Moisture present in motor/control module. | ||
– “Hunts” or “puffs” at high CFM (speed). | – Incorrect or dirty filter(s). | |
– Incorrect supply or return ductwork. | ||
– Incorrect blower speed setting. | ||
– Motor starts, but runs erratically. | – Stays at low CFM despite system call for cool or heat CFM. | – 24 Vac wires miswired or loose. |
– “R” missing/not connected at motor. | ||
– Fan is delay mode. | ||
– Stays at high CFM. | – “R” missing/not connected at motor. | |
– Fan is delay mode. | ||
– Blower won’t shut off. | – Current leakage from controls into G, V, or W. | |
– Air noise. | – High static creating high blower speed. | |
– Incorrect supply or return ductwork. | ||
– Incorrect or dirty filter(s). | ||
– Incorrect blower speed setting. | ||
– Excessive noise. | – Noisy blower or cabinet. | – Loose blower housing, panels, etc. |
– High static creating high blower speed. | ||
– Air leaks in ductwork, cabinets, or panels. | ||
– “Hunts” or “puffs’ at high CFM (speed). | – High static creating high blower speed. | |
– Incorrect or dirty filter(s). | ||
– Incorrect supply or return ductwork. | ||
– Incorrect blower speed setting. | ||
– Evidence of Moisture. | – Motor failure or malfunction has occurred and moisture is present. | – Moisture in motor/control module. |